9.2.2. ModbusControl&MonitoringRegisters
ThefollowingisalistofaccessibleModbusRegistersavailableintheDrive.
WhenModbusRTUisconfiguredastheFieldbusoption,allofthelistedregisterscanbeaccessed.
Registers1and2canbeusedtocontrolthedriveprovidingthatModbusRTUisselectedasthe
primarycommandsource(P112=4)
andnoFieldbusOptionModuleisinstalledinthedriveOptionSlot.
Register3canbeusedtocontroltheoutputtorquelevelprovidingthat
o ThedriveisoperatinginVectorSpeedorVectorTorquemotorcontrolmodes(P401=
1or2)
o Thetorquecontrollerreference/limitissetfor‘Fieldbus’(P406=3)
Register4canbeusedtocontroltheaccelerationanddecelerationrateofthedriveprovidingthatFieldbusRampControlisenabled
(P507=1)
Registers6to24can
bereadregardlessofthesettingofP112
Register
Number
UpperByte LowerByte Read
Write
Notes
1
CommandControlWord R/W CommandcontrolwordusedtocontroltheDrivewhenoperatingwithModbusRTU.
TheControlWordbitfunctionsareasfollows:‐
Bit0:Run/Stopcommand.Setto1toenablethedrive.Setto0tostopthedrive.
Bit1:Faststoprequest.
Setto1toenabledrivetostopwith2
nd
decelerationramp.
Bit2:Resetrequest.Setto1inordertoresetanyactivefaultsortripsonthedrive.
Thisbitmustberesettozerooncethefaulthasbeencleared.
Bit3:Coaststoprequest.Setto1toissueacoaststopcommand.
2 CommandSpeedReference R/W SetpointmustbesenttothedriveinHztoonedecimalplace,e.g.500=50.0Hz
3 CommandTorqueReference R/W Setpointmustbesenttothedrivein%toonedecimalplace,e.g.2000=200.0%
4
CommandRamptimes R/W Thisregisterspecifiesthedriveaccelerationanddecelerationramptimesusedwhen
FieldbusRampControlisselected(P508=1)irrespectiveofthesettingofP112.The
inputdatarangeisfrom0to60000(0.00sto600.00s)
6
Errorcode Drivestatus R Thisregistercontains2bytes.
TheLowerBytecontainsan8bitdrivestatuswordasfollows:‐
Bit0:0=DriveDisabled(Stopped),1=DriveEnabled(Running)
Bit1:0=DriveHealthy,1=DriveTripped
TheUpperBytewillcontaintherelevantfaultnumberintheeventofadrivetrip.
RefertosectionError!Referencesourcenotfound.foralistoffaultcodesand
diagnosticinformation
7 OutputFrequency R Outputfrequencyofthedrivetoonedecimalplace,e.g.123=12.3Hz
8 OutputCurrent R Outputcurrentofthedrivetoonedecimalplace,e.g.105=10.5Amps
9 OutputTorque R Motoroutputtorqueleveltoonedecimalplace,e.g.474=47.4%
10 OutputPower R Outputpowerofthedrivetotwodecimalplaces,e.g.1100=11.00kW
11 DigitalInputStatus R RepresentsthestatusofthedriveinputswhereBit0=DigitalInput1etc.
20 Analog1Level R AnalogInput1AppliedSignallevelin%toonedecimalplace,e.g.1000=100.0%
21 Analog2Level R AnalogInput2AppliedSignallevelin%toonedecimalplace,e.g.1000=100.0%
22 PreRampSpeedReference R Internaldrivefrequencysetpoint
23 DCbusvoltages R MeasuredDCBusVoltageinVolts
24 Drivetemperature R MeasuredHeatsinkTemperaturein°C
9.2.3. ModbusParameterAccess
AllUserAdjustableparameters(Groups1to5)areaccessiblebyModbus,exceptthosethatwoulddirectlyaffecttheModbuscommunications,
e.g.
P501CommunicationProtocolSelect
P502DriveFieldbusAddress
P503ModbusRTUBaudRate
P504ModbusRTUDataFormat
Allparametervalues
canbereadfromthedriveandwrittento,dependingontheoperatingmodeofthedrivesomeparameterscannotbe
changedwhilstthedriveisenabledforexample.
WhenaccessingadriveparameterviaModbus,theRegisternumberfortheparameteristhesameastheparameternumber,
E.g.ParameterP101=ModbusRegister101.
ModbusRTUsupportssixteenbitintegervalues,hencewhereadecimalpointisusedinthedriveparameter,theregistervaluewillbemultiplied
byafactoroften,
E.g.ReadValueofP101=500,thereforethisis50.0Hz.
ForfurtherdetailsoncommunicatingwithDriveusing ModbusRTU,pleaserefertoyourlocaldistributororSalesPartner.