4.4. Operationof3PhasedrivesfromaSinglePhaseSupply
AspecialfunctionofDriveallowsalldrivesdesignedforoperationon3phasesuppliestobeoperatedonasinglephasesupplyofthecorrect
ratedvoltageatupto50%ofthenominalcapacity.
ForExample,ModelNumberODP‐2‐64450‐3KA4Ncanbeoperatedonasinglephasesupply,380–480volts,withthemaximumoutputcurrent
limitedto45Amps
ThesupplyshouldbeconnectedtotheL1andL2terminalsofthedrive.
4.5. DriveandMotorConnection
• Thedriveinherentlyproducesfastswitchingoftheoutputvoltage(PWM)tothemotorcomparedtothemainssupply,formotors
whichhavebeenwoundforoperationwithavariablespeeddrivethenthereisnopreventativemeasuresrequired,howeverifthe
qualityofinsulationisunknownthenthemotor
manufacturershouldbeconsultedandpreventativemeasuresmayberequired.
• ThemotorshouldbeconnectedtotheDriveU,V,andWterminalsusingasuitable3or4corecable.Wherea3corecableisutilised,
withtheshieldoperatingasanearthconductor,theshieldmust
haveacrosssectionalareaatleastequaltothephaseconductors
whentheyaremadefromthesamematerial.Wherea4corecableisutilised,theearthconductormustbeofatleastequalcross
sectionalareaandmanufacturedfromthesamematerialasthephaseconductors.
• The
motorearthmustbeconnectedtooneoftheDriveearthterminals.
• ForcompliancewiththeEuropeanEMCdirective,asuitablescreened(shielded)cableshouldbeused.Braidedortwistedtype
screenedcablewherethescreencoversatleast85%ofthecablesurfacearea,designedwithlowimpedance
toHFsignalsare
recommendedasaminimum.Installationwithinasuitablesteelorcoppertubeisgenerallyalsoacceptable.
• ThecablescreenshouldbeterminatedatthemotorendusinganEMCtypeglandallowingconnectiontothemotorbodythroughthe
largestpossiblesurfacearea
• Wheredrives
aremountedinasteelcontrolpanelenclosure,thecablescreenmaybeterminateddirectlytothecontrolpanelusinga
suitableEMCclamporgland,asclosetothedriveaspossible.
• ForIP55drives,connectthemotorcablescreentotheinternalgroundclamp
4.6. MotorTerminalBoxConnections
Mostgeneralpurposemotorsarewoundforoperationondualvoltagesupplies.Thisisindicatedonthenameplateofthemotor
ThisoperationalvoltageisnormallyselectedwheninstallingthemotorbyselectingeitherSTARorDELTAconnection.STARalwaysgivesthe
higherofthetwovoltageratings.
IncomingSupplyVoltage MotorNameplateVoltages Connection
230 230/400
Delta
400 400/690
400 230/400 Star
4.7. MotorThermistorConnection
4.7.1. InternalThermaloverloadprotection.
Thedrivehasanin‐builtmotorthermaloverloadfunction;thisisintheformof an“I.t‐trP”tripafterdelivering>100%ofthevaluesetinP1‐08
forasustainedperiodoftime(e.g.150%for60seconds).
4.7.2. MotorThermistorConnection
Whereamotorthermistoristobeused,itshouldbeconnectedasfollows:
AdditionalInformation
• CompatibleThermistor:PTCType,2.5kΩtriplevel
• UseasettingofP1‐13thathasInput5functionasExternalTrip,e.g.P1‐13