APPLICATIONNOTEAN‐BEI‐H2‐038 Date:15/02/12
AN‐BEI‐H2‐038ModbusRTUControlandRegisterMapping
7
Group2:Extendedparameterset(Level2)
Parameter Register
Number
Description Range Scaling Type
P2‐01 201 Presetspeed1 ‐7200to7200(LimitedbyP1‐01) 3000=50.0Hz S16
P2‐02 202 Presetspeed2 ‐7200to7200(LimitedbyP1‐01) 3000=50.0Hz S16
P2‐03 203 Presetspeed3 ‐7200to7200(LimitedbyP1‐01) 3000=50.0Hz S16
P2‐04 204 Presetspeed4 ‐7200to7200(LimitedbyP1‐01) 3000=50.0Hz S16
P2‐05 205 Presetspeed5 ‐7200to7200(LimitedbyP1‐01) 3000=50.0Hz S16
P2‐06 206 Presetspeed6 ‐7200to7200(LimitedbyP1‐01) 3000=50.0Hz S16
P2‐07 207 Presetspeed7 ‐7200to7200(LimitedbyP1‐01) 3000=50.0Hz S16
P2‐08 208 Presetspeed8 ‐7200to7200(LimitedbyP1‐01) 3000=50.0Hz S16
P2‐09 209 Skipfrequencycentrepoint 0to7200(LimitedbyP1‐01) 3000=50.0Hz S16
P2‐10 210 Skipfrequencyband 0to7200(LimitedbyP1‐01) 3000=50.0Hz S16
P2‐11 211 Analogoutput1functionselect
DigitalMode(0Vor24Vonly)
0:Driverunning
1:Drivehealthy
2:Motorattargetspeed
3:MotorSpeed>0
4:MotorSpeed>limit
5:MotorCurrent>limit
6:MotorTorque>limit
7:2
nd
Analoginput>limit
(LimitsetbyP2‐18,P2‐19)
AnalogMode
8:Speed
9:Current
10:Torque
11:Power
U16
P2‐12 212 Analogoutput1format
0=0…10V
1=10…0V
2=0‐20mA
3=20‐0mA
4=4‐20mA
5=20‐4mA
U16
P2‐13 213 Analogoutput2functionselect
DigitalMode(0Vor24Vonly)
0:Driverunning
1:Drivehealthy
2:Motorattargetspeed
3:MotorSpeed>0
4:MotorSpeed>limit
5:MotorCurrent>limit
6:MotorTorque>limit
7:2
nd
Analoginput>limit
(LimitsetbyP2‐18,P2‐19)
AnalogMode
8:Speed
9:Current
10:Torque
11:Power
U16
P2‐14 214 Analogoutput2format
0=0…10V
1=10…0V
2=0‐20mA
3=20‐0mA
4=4‐20mA
5=20‐4mA
U16
P2‐15 215 Userrelay1outputfunctionselect
0:Driverunning
1:Drivehealthy
2:Motorattargetspeed
3:MotorSpeed>0
4:MotorSpeed>limit
5:MotorCurrent>limit
6:MotorTorque>limit
7:2
nd
Analoginput>limit
U16
P2‐16 216 Userrelay1upper limit P2‐17to2000 1=0.1% U16
P2‐17 217 Userrelay1lowerlimit 0toP2‐16 1=0.1% U16