Strany 2 - IP55 Quick Start Up Guide

User Guide Revision 1.12 10 2.1.3. IP55 Enclosed Units 2.1.4. IP40 Enclosed Units 2.2. Identifying the Drive by Model Number Each drive can be i

Strany 3 - IP66 Quick Start Up Guide

User Guide Revision 1.12 11 3. Mechanical Installation 3.1. General  The drive should be mounted in a vertical position only on a flat, flame resi

Strany 4 - IP20 Quick Start Up Guide

User Guide Revision 1.12 12 3.5. Mechanical dimensions and mounting – IP66 Units Drive Size A B C D E F G H I mm in

Strany 5

User Guide Revision 1.12 13 Control Terminal Torque Settings: All Sizes: 0.8 Nm (7 lb-in) Power Terminal Torque Settings: Frame Size 4: 1.2 – 1

Strany 6 - User Guide Revision 1.12

User Guide Revision 1.12 14 3.8. Guidelines for Enclosure mounting (IP20 Units)  Installation should be in a suitable enclosure, according to

Strany 7

User Guide Revision 1.12 15 3.10. Guidelines for mounting IP40 Units  Before mounting the drive, ensure that the chosen location meets the enviro

Strany 8 - 1. Introduction

User Guide Revision 1.12 16 3.11. Removing the Terminal Cover 3.11.1. Frame Size 2 3.11.2. Frame Size 3 3.11.3. Frame Size 4 3.11.4. Frame Size

Strany 9 - 2.1. Drive model numbers

User Guide Revision 1.12 17 3.11.5. Frame Size 6 3.11.6. Frame Size 7 Using a suitable flat blade screwdriver, rotate the two retaining screws i

Strany 10 - 2.1.4. IP40 Enclosed Units

User Guide Revision 1.12 18 3.11.7. Frame Size 8 Open Access to Control Terminal Wiring and Options Module Slot Access to Power and Motor Wir

Strany 11 - 3. Mechanical Installation

User Guide Revision 1.12 19 3.12. Gland Plate and Lock Off The use of a suitable gland system is required to maintain the appropriate IP / Nema rat

Strany 12

User Guide Revision 1.12 2 IP55 Quick Start Up Guide

Strany 13

User Guide Revision 1.12 20 4. Electrical Installation 4.1. Grounding the Drive This manual is intended as a guide for proper installation. The M

Strany 14

User Guide Revision 1.12 21 4.2. Wiring Precautions Connect the drive according to section 4.3 and 4.4, ensuring that motor terminal box connections

Strany 15

User Guide Revision 1.12 22 4.5. Motor Terminal Box Connections Most general purpose motors are wound for operation on dual voltage supplies. This

Strany 16

User Guide Revision 1.12 23 4.7. Control Terminal Wiring  All analog signal cables should be suitably shielded. Twisted pair cables are recommended

Strany 17 - 3.11.6. Frame Size 7

User Guide Revision 1.12 24 5. Managing the Keypad The drive is configured and its operation monitored via the built in keypad and display. IP20

Strany 18 - 3.11.7. Frame Size 8

User Guide Revision 1.12 25 5.3. Advanced Keypad Operation Short Cuts – Standard LED Keypad (IP20 Drives) Function When Display shows... Press... Res

Strany 19

User Guide Revision 1.12 26 Main Displayed Parameter Shows which of the selectable parameters is currently being shown on the main display, e.g. Mot

Strany 20 - 4. Electrical Installation

User Guide Revision 1.12 27 5.8. Resetting Parameters to Factory Default Settings – Standard OLED Keypad (IP55 and IP66 Drives) Hold down

Strany 21 - 4.2. Wiring Precautions

User Guide Revision 1.12 28 5.10. Changing the Language on the OLED Display – Standard OLED Keypad (IP55 and IP66 Drives) Hold down the

Strany 22

User Guide Revision 1.12 29 6. Commissioning 6.1. General The following guidelines apply to all applications 6.1.1. Entering the motor nameplate in

Strany 23

User Guide Revision 1.12 3 IP66 Quick Start Up Guide HVAC Display (Status, Diagnostic

Strany 24 - 5. Managing the Keypad

User Guide Revision 1.12 30 7. HVAC Specific Feature Setup (Menu 8) The drive has several features inbuilt into the drive standard operating softwa

Strany 25

User Guide Revision 1.12 31  Set Basic parameters P1-01 to P1-10. Energy Optimiser P1-06 must remain disabled.  Set Parameter P1-14= 101 to allow

Strany 26

User Guide Revision 1.12 32 When the system is enabled the master drive will check the run time clocks for all drives in the network which ar

Strany 27

User Guide Revision 1.12 33 P2-15 Relay output 1 function select 14 / 15 10 P2-18 Relay output 2 function select 16 / 17 / 18 10 When the maintenanc

Strany 28

User Guide Revision 1.12 34 A detection tolerance for the Load Profile Monitoring Function is set within parameter P8-07. Parameter P

Strany 29 - 6. Commissioning

User Guide Revision 1.12 35 The Pump Cleaning cycle is defined by setting two segment speeds, a ramp time (used for acceleration and deceleration),

Strany 30 - Quick Setup Overview:

User Guide Revision 1.12 36 Operational Overview: The time period to trigger the pump Stir function is entered into parameter P8-01 (Stir Function

Strany 31

User Guide Revision 1.12 37 The main selector switch selects between the following modes.  System Off : Drive is powered off; Bypass contactor i

Strany 32 - Value set

User Guide Revision 1.12 38 Bypass Mode on Fault is enabled by setting parameter P8-11=1 (enabled). Once enabled the drive will switch to bypass mod

Strany 33

User Guide Revision 1.12 39  P9-32: Fire Mode input source can be set via P9-32 to an available digital input. Advanced level security (default P1

Strany 34 - 7.5. Pump Clean Function

User Guide Revision 1.12 4 IP20 Quick Start Up Guide AC Supply Connection Supply Voltage 3 Phase Units : Connect L1 L2 L3, PE 200

Strany 35 - 7.6. Pump Stir Function

User Guide Revision 1.12 40  Set parameter P9-32 to an available digital input value. Note, P1-13 must be set to 0. Any other digital inputs requi

Strany 36 - 7.7. Bypass Control Function

User Guide Revision 1.12 41 The function uses the Boost Voltage on the drive reaching zero speed in order to create a current and maintain an appropr

Strany 37

User Guide Revision 1.12 42 8. PID Control Applications 8.1. Overview The PID Controller is a mathematical function designed to automate adjustment

Strany 38 - 7.8. Fire Mode Function

User Guide Revision 1.12 43 8.2.3. PID Operating Mode Selection For default operation the drive response to an increase in feedback signal is to dec

Strany 39

User Guide Revision 1.12 44 point). For dynamic systems which respond quickly, the value will need to be shorter. Slow response systems, such as tem

Strany 40

User Guide Revision 1.12 45 The execution time for both the sleep and wake boost functions (P6-11 and P6-12) include the time taken to accelerate t

Strany 41

User Guide Revision 1.12 46 8.4. PID Pipe Prime (Fill) Mode with Pipe Break Detection. Pump prime mode allows starting of the pump in a safely contr

Strany 42 - 8. PID Control Applications

User Guide Revision 1.12 47 9. Parameters 9.1. Parameter Set Overview The drive Parameter set consists of 9 groups as follows:  Group 1 – Basic P

Strany 43

User Guide Revision 1.12 48 P1-11 Voltage Boost 0 15 – 30% [Drive Dependent] 0.5 – 2.5% [Drive Dependent] % Voltage boost is used to increase the ap

Strany 44

User Guide Revision 1.12 49 10. Digital Input Functions 10.1. Digital Input Configuration Parameter P1-13 P1-13 *(2) Local (Hand) Control Function

Strany 45 - 8.3. Application Example

User Guide Revision 1.12 5 Declaration of Conformity: The Manufacturer hereby states that the HVAC Inverter H2 product range conforms to the releva

Strany 46

User Guide Revision 1.12 50 11. Extended Parameters 11.1. Parameter Group 2 - Extended parameters Par Parameter Name Minimum Maximum Default Units

Strany 47 - 9. Parameters

User Guide Revision 1.12 51 P2-12 Analog Output 1 Format (Terminal 8) - -  - = 0 to10V,  = 10 to 0V,  = 0 to 20mA 

Strany 48 - 0.5 – 2.5%

User Guide Revision 1.12 52 P2-18 Relay Output 2 Function (Terminals 17 & 18) 0 8 0 - Selects the function assigned to Relay Output 2. The rel

Strany 49 - 10. Digital Input Functions

User Guide Revision 1.12 53 P2-30 Analog Input 1 Format (Terminal 6) - -  -  = 0 to 10 Volt Signal (Uni-polar)  = 10 to 0 Volt Si

Strany 50 - 11. Extended Parameters

User Guide Revision 1.12 54 P2-39 Parameter Access Lock 0 1 0 - 0 : Unlocked. All parameters can be accessed and changed 1 : Locked. Parameter value

Strany 51 - = 4 to 20mA

User Guide Revision 1.12 55 P3-15 2nd PID Digital Reference Value 0.0 100.0 0.0 % When P3-05 = 0, and the 2nd digital reference is selected (see Dig

Strany 52 - [Drive Dependent]

User Guide Revision 1.12 56 P5-08 Fieldbus Module PDO4 0 7 1 - When using an optional Fieldbus interface, this parameter configures the parameter so

Strany 53

User Guide Revision 1.12 57 P6-10 PLC Function Enable 0 1 0 - This parameter enables the PLC function support and must be set to 1 before any PLC pro

Strany 54

User Guide Revision 1.12 58 P8-05 Clean Function Ramp Time 0.0 6000 30 Secs Independent ramp rate used only for the pump automatic cleaning function

Strany 55

User Guide Revision 1.12 59 P8-17 Assist Pump Start Speed P8-18 P1-01 0 Hz / RPM H2 drive upper speed Staging threshold. When the drive output increa

Strany 56

User Guide Revision 1.12 6 1. Introduction ...

Strany 57

User Guide Revision 1.12 60 11.9. Parameter Group 0 – Monitoring Parameters (Read Only) Par Parameter Name Minimum Maximum Default Units P0-01 Anal

Strany 58

User Guide Revision 1.12 61 P0-29 Drive Type - - - - Displays the type details of the drive: Three entry display: First display = Frame size and inp

Strany 59

User Guide Revision 1.12 62 P0-57 Ud / Uq - - - - Internal Value, Contact your local Drive Distributor P0-58 Load Torque Profile Current Values - -

Strany 60

User Guide Revision 1.12 63 12. Serial communications 12.1. RS-485 communications The drive has an RJ45 connector located within the wiring enclosur

Strany 61

User Guide Revision 1.12 64 12.2.2. Modbus Control & Monitoring Registers The following is a list of accessible Modbus Registers available in th

Strany 62

User Guide Revision 1.12 65 13. Technical Data 13.1. Environmental Ambient temperature range: Operational: IP20 -10 … 50C / Max 55C

Strany 63 - Warning:

User Guide Revision 1.12 66 200 - 240 Volt (+ / - 10%) 3 Phase Input, 3 Phase Output kW HP Nominal Input Current Fuse Or MCB (Type B) Supply Cable

Strany 64

User Guide Revision 1.12 67 13.5. Additional Information for UL Approved Installations Optidrive HVAC is designed to meet the UL requirements. In o

Strany 65 - 13. Technical Data

User Guide Revision 1.12 68 14. Parameter Change Tables The following tables can be used to enter parameter changes made to the drive as a result of

Strany 66

User Guide Revision 1.12 69 P8-15 DOL Pump Availability Number P9-17 Speed Source 8 P8-16 Enabled Switch Over Time P9-18 Speed Select Input 0

Strany 67

User Guide Revision 1.12 7 10.1. Digital Input Configuration Parameter P1-13 ...

Strany 68 - 14. Parameter Change Tables

User Guide Revision 1.12 70 15. Troubleshooting 15.1. Fault messages Fault Code No. OLED Message Description Corrective Action 00 No Fault N

Strany 69

User Guide Revision 1.12 71 Fault Code No. OLED Message Description Corrective Action 20 User Parameter Default User Parameter Defaults User Pa

Strany 70 - 15. Troubleshooting

User Guide Revision 1.12 72  82-H2MAN-BE_V1.11

Strany 71

User Guide Revision 1.12 8 1. Introduction 1.1. Important safety information Please read the IMPORTANT SAFETY INFORMATION below, and all Warning a

Strany 72 - 

User Guide Revision 1.12 9 2. General Information and Ratings 2.1. Drive model numbers 2.1.1. IP20 Enclosed Units 2.1.2. IP66 Enclosed Units 20