APPLICATIONNOTEAN‐BEI‐P2‐038 Date:15/02/12
AN‐BEI‐P2‐038ModbusRTUControlandRegisterMapping
12
Group6:AdvancedParameterset(Level3)
Par Register Description Range Scaling Type
P6‐01 601 FirmwareUpgradeenable
0:Disabled
1:Enable(IOandDSP)
2:Enable(IOonly)
3:Enable(DSPonly)
U16
P6‐02 602 Autothermalmanagement
0:Disable
1:Enable
WORD
P6‐03 603 Auto‐resetdelaytime 1to60 U16
P6‐04 604 Userrelayhysteresisband 0‐ 250 1=0.1% U16
P6‐05 605 Encoderfeedbackenable
0:Disabled
1:Enable
WORD
P6‐06 606 EncoderPPR 0to 65535 U16
P6‐07 607 Speederrortriplevel 0 to500 1=0.1% U16
P6‐08 608 Maxspeedreffrequency 0,5 to20 U16
P6‐09 609 SpeedDroopControl 0 to250 1=0.1% U16
P6‐10 610 EnablePLCoperation
0:Disable
1:Enable
WORD
P6‐11 611 Speedholdtimeonenable 0to2500 1=0.1s U16
P6‐12 612 Speedholdtimeondisable 0 to2500 1=0.1s U16
P6‐13 613 Hoistmodebrakereleasedelay 0to50 1=0.1s U16
P6‐14 614 Hoistmodebrakeapplydelay 0to50 1=0.1s U16
P6‐15 615 Torquethresholdforhoistbrakerelease 0to2000 1=0.1% U16
P6‐16 616 Torquethresholdtimeout 0to250 1=0.1s U16
P6‐17 617 MaxTorquelimittimeout 0to250 1=0.1s U16
P6‐18 618 DCinjectionbrakingvoltage
0:Auto
0to250
0=Auto
1=0.1%
U16
P6‐19 619 Brakeresistorvalue 0,Minvalueto200 1=1 U16
P6‐20 620 Brakeresistorpower 0to20000 1=0.01kw U16
P6‐21 621 BrakechopperUTdutycycle 0to200 1=0.1% U16
P6‐22 622 Resetcoolingfanrun‐time
0:Disable
1:Enable
WORD
P6‐23 623 ResetkWhmeter
0:Disable
1:Enable
WORD
P6‐24 624 Servicetimeinterval
0…60000h
(0=disabled)
1=1
U16
P6‐25 625 Resetserviceindicator
0:Disable
1:Reset
1=1
WORD
P6‐26 626 Analogoutput1scaling 0to5000 1=0.1 U16
P6‐27 627 Analogoutput1offset‐5000to5000 1=0.1% S16
P6‐28 628 P0‐80displayvalueindex 0to127 U16
P6‐29 629 SaveUserParametersasdefault
0:Disable
1:Enable
WORD
P6‐30 630 Level3accesscode 0to9999 U16
Group7:MotorControlParameterset(Level3)
Parameter
Number
Register
Number
Description Range Scaling Type
P7‐01 701 MotorStatorresistance Drivedependent 1=0.001ohm U16
P7‐02 702 MotorRotorresistance Drivedependent 1=0.001ohm U16
P7‐03 703 Motorstatorinductance Drivedependent 1=0.0001H U16
P7‐04 704 MotorMagnetisingCurrent Drivedependent 1=0.1A U16
P7‐05 705 MotorLeakageCoefficient 0 to250 1=0.001 U16
P7‐06 706 MotorStatorinductance(PMonly) Drivedependent 1=0.0001H U16
P7‐07 707 Enhancedgeneratorcontrol
0:Disable
1:Enable
WORD
P7‐08 708 Parameteradaptation
0:Disable
1:Enable
WORD
P7‐09 709 Overvoltagecurrentlimit 0.0to100%ofmotorratedcurrent 1=0.1% U16
P7‐10 710 LoadInertiaFactor 0to600 1=1 U16
P7‐11 711 Pulsewidthminimumlimit 0 to500 (Time=value*16.67ns) 1=1 U16
P7‐12 712 V/Fmodemagnetisingperiod 0to2000 U16
P7‐13 713 VectorSpeedControllerD‐Gain 0to4000 1=0.1% U16
P7‐14 714 Lowfrequencytorqueboost 0 to1000 1=0.1% U16
P7‐15 715 Torqueboostfrequencylimit 0 to500 1=0.1% U16